The U.S. Cybersecurity and Infrastructure Security Agency (CISA)
has warned of critical security shortcomings in GE’s Universal
Relay (UR) family of power management devices.

“Successful exploitation of these vulnerabilities could allow an
attacker to access sensitive information, reboot the UR, gain
privileged access, or cause a denial-of-service condition,” the
agency said[1]
in an advisory published on March 16.

GE’s universal relays enable[2]
integrated monitoring and metering, high-speed communications, and
offer simplified power management for the protection of critical
assets.

The flaws, which affect a number of UR advanced protection and
control relays, including B30, B90, C30, C60, C70, C95, D30, D60,
F35, F60, G30, G60, L30, L60, L90, M60, N60, T35 and T60, were
addressed by GE with the release of an updated version of the
UR firmware[3]
(version 8.10) made available on December 24, 2020.

The patches resolve a total of nine vulnerabilities, the most
important of which concerns an insecure default variable[4] initialization,
referring to the initialization of an internal variable in the
software with an insecure value. The vulnerability (CVE-2021-27426)
is also rated 9.8 out of 10, making it a critical issue.

“By sending a specially crafted request, an attacker could
exploit this vulnerability to bypass access restrictions,” IBM noted[5]
in its alert.A second severe vulnerability relates to unused
hard-coded credentials in the bootloader binary (CVE-2021-27430,
CVSS score 8.4), which could be exploited by an attacker “with
physical access to the UR [Intelligent Electronic Device] can
interrupt the boot sequence by rebooting the UR.”

Also fixed by GE is another high severity flaw (CVE-2021-27428,
CVSS score 7.5) that could permit an unauthorized user to upgrade
firmware without appropriate privileges.

Four other vulnerabilities involve two improper input
validations (CVE-2021-27418, CVE-2021-27420) and two flaws
concerning exposure of sensitive information to unauthorized
parties (CVE-2021-27422, CVE-2021-27424), thereby exposing the
device to cross-site scripting attacks, permitting an attacker to
access critical information without authentication, and even render
the webserver unresponsive.

Lastly, all versions of UR firmware prior to 8.1x were found to
use weak encryption and MAC algorithms for SSH communication,
making them more vulnerable to brute-force attacks.

“CISA recommends users take defensive measures to minimize the
risk of exploitation of these vulnerabilities,” the agency said.
“Minimize network exposure for all control system devices and/or
systems and ensure that they are not accessible from the Internet,
[and] locate control system networks and remote devices behind
firewalls and isolate them from the business network.”